FLAG POLE
GREEN AREA GREEN AREA
R O A D R O A D
1 5 10 12
13 15
GREEN AREA
GREEN AREA
GREEN AREA
IN SIDE
OUT SIDE
FLAG POLE
GREEN AREA GREEN AREA
R O A D R O A D
1 5 10 12
13 15
GREEN AREA
GREEN AREA
GREEN AREA
IN SIDE
OUT SIDE
EP
EP
EP
EP
EP
EP
WAREHOUSE 1
PL+6.273
PL+6.289
PL+6.361
PL+6.382
(PL+6.672)
(PL+6.685) (PL+6.608)
(PL+6.607) (PL+6.746)
PL+6.354
PL+6.421
PL+6.348
PL+6.272
PL+6.339
PL+6.342
ELECTRIC POLE
(PL+6.676) (PL+6.706) (PL+6.65)
(PL+6.357) (PL+6.758) (PL+6.68) (PL+7.003)
PL+6.374
(PL+6.326)
(PL+6.353)
3% (PL+6.953)
BENCH MARK
(PL+6.140)
PL+6.433
PL+6.438
PL+6.435
(PL+6.806)
OFFICE
UTILITY
BUILDING
WAREHOUSE 2
ROOM 1 ROOM 2
FL+0.00
FLAG POLE
GREEN AREA GREEN AREA
1 5 10 12
13 15
GREEN AREA
GREEN AREA
GREEN AREA
IN SIDE
OUT SIDE
FLAG POLE
GREEN AREA GREEN AREA
1 5 10 12
13 15
GREEN AREA
GREEN AREA
GREEN AREA
IN SIDE
OUT SIDE
EP
EP
EP
EP
EP
EP
WAREHOUSE 1
(PL+6.672)
(PL+6.685) (PL+6.608)
(PL+6.607) (PL+6.746)
(PL+6.676) (PL+6.706) (PL+6.65)
(PL+6.357) (PL+6.758) (PL+6.68) (PL+7.003)
PL+6.374
(PL+6.326)
(PL+6.353)
3% (PL+6.953)
PL+6.433
PL+6.438
PL+6.435
(PL+6.806)
PC FENCE, H=2400
OFFICE
UTILITY
BUILDING
WAREHOUSE 2
ROOM 1 ROOM 2
FL+0.00
RU FEP∅40 x3
RU FEP∅40 x2 RU FEP∅40 x2 RU FEP∅40 x2
FDB-ERM
2
FDB-GH
1
FDB-ERM
11
FDB-GH
3
FDB-GH
3
FDB-GH
3
FDB-GH
3
FDB-GH
5
FDB-GH
5
FDB-GH
5
FDB-GH
5
FDB-GH
5
RU FEP∅40 x3
R Y B FUSE
ATS
4P 450A
R Y B FUSE
MCCB,4P
450A
R Y B FUSE
VSS V
FUSE
ASS A
FUSE
CT x3
450/5A 15VA
R Y B FUSE
APFC
OFFICE LIGHTING/SERVER/FP COMMON LIGHTING/AC
LV RECEIVING
ATS-1
MCCB,4P
450A
/ (NON ESSENTIAL LOAD)
DPM
CT x3
500/5A 15VA
NCT
51G
51
FACTORY FENCE
EHV TR-1 (200KVA)
27
MCCB,4P
450A
MC,3P
400A
EXISTING POLE
MCCB
3P 50AT
MC C
3P 60AT
TOTAL = 189 KVAR
SR1
3∅ 440V 6%
PFI MCCB
4P 300A
MCCB,4P
300A
MCCB,4P
100A
PRODUCTION / FACILITY
SPARE
EHV TR-2 (700 KVA) EHV MAIN INCOMING
EXISTING 33KV POWER COMPANY OH LINE
BSEZ COMPANY OH LINE 33 KV
BY ELECTRICAL CONTRACTOR
LA
EMDB MDB
1 6
UVWN
1
UVWN
2
UVWN
3
UVWN
4
UVWN
5
UVWN
6
UVWN
8
UVWN
7
UVWN
10
UVWN
9
UVWN
11
UVWN
12
UVWN
13
UVWN
14
UVWN
15
MCCB 2
4P 63AT
MCCB 4
4P 63AT
MCCB 5
4P 63AT
MCCB 1
4P 100AT
FDB-2
MCC-1 MCCB 3
4P 150AT
FDB-1
MCCB 6
4P 50AT
MCC-2
DB-QC-PANEL
FDB-GH
PP-1 MCCB 7
3P 100AT
MCCB 8
3P 63AT
FDB-ERM
MCCB 11
3P 800AT
SOLAR MCCB 12
4P 63AT
MCCB 13
3P 50AT
SPARE MCCB 14
3P 32AT
SPARE MCCB 15
3P 32AT
MCCB 9
3P 63AT
MCCB 10
4P 40AT
Battery
FDB-GEN
FIRE PUMP
XLPE
35°-4C
+E.16
XLPE
35°-4C
+E.16
XLPE
16°-4C
+E.16
XLPE
16°-4C
+E.16
XLPE
120°-1C x4
+E.70
XLPE
25°-4C
+E.16
XLPE
16°-4C
+E.16
XLPE
16°-4C
+E.16
XLPE
16°-4C
+E.16
XLPE
70°-4C
+E.35
XLPE
16°-4C
+E.16
NO
ESSENTIAL
CLOSE WHEN
CITY POWER "ON"
CB
4P
MC,
4P
LOAD
LOAD
LOAD
LOAD
FDB-1
CB
4P
MC,
4P
LOAD
LOAD
LOAD
LOAD
FDB-2
CB
4P
MC,
4P
LOAD
LOAD
LOAD
LOAD
MCC-1
CB
4P
MC,
4P
LOAD
LOAD
LOAD
LOAD
FDB-GH
NO
NC
NO NO NO
NON ESSENTIAL
SC1
3∅ 7%
31.5kVAR
MCCB
3P 50AT
MC C
3P 60AT
SR6
3∅ 440V 6%
SC6
3∅ 7%
31.5kVAR
TR-QC
XLPE
16°-4C
+E.16
XLPE
16°-4C
+E.16
DTR 50KVA